상세 보기
초록
The purpose of this study is to understand the indoor thermal environment in the earth brick wall building what is called a ecological Architecture. To investigate thermal performances of the earth brick walls, it measured indoor and outdoor air temperature, relative humidity, globe temperature and PMV in reference house. The result of this study were summarized as the followings; 1) When the outdoor average air temperature was 21.8℃, livingroom was 24.9℃, kitchen was 25.1℃ and 2nd floor room was 25.6℃ at 150 cm height from the floor. 2) Although the average outdoor relative humidity was 78%, the livingroom was 67.5%. 3) As the air temperature difference between at the top and bottom was 0.6℃ in living room, this value was below 1 % of PPD by ASHRAE Handbook. 4) Predicted Mean Vote(PMV) by ISO-7730 was +0.41.
키워드
- 제목
- 황토벽돌벽 주택의 실내온열환경에 관한 연구
- 제목 (타언어)
- A Study on the Indoor Thermal Environment of House Using Earth Brick Wall
- 저자
- 이재윤
- 발행일
- 2004-02
- 유형
- Y
- 저널명
- 한국주거학회논문집
- 권
- 15
- 호
- 1
- 페이지
- 25 ~ 32