상세 보기
교육시설에 적용 가능한 태양열 흡수식 냉각 시스템
- 윤성민;
- 백인수;
- 한영태;
- 남효갑
초록
Performance of a small-capacity solar absorption cooling system was investigated experimentally. Ten sets of evacuative-tube solar-heat collectors and a 5 kW single-stage absorption cooler were combined to produce a hybrid cooling system. The performance of the cooling system was measured using a fan-coil unit installed in a small plastic storage. It was found from the test on a sunny day of May that when the temperature of the hot water supplied from the solar collectors to the generator of the absorption cooler reached 60 ℃, the absorption cooler started cooling and the cold water temperature measured from the fan-coil unit reached 18℃. The COP, which is defined as the ratio of the cooling power to the total electrical power input was higher than 1.0.
키워드
- 제목
- 교육시설에 적용 가능한 태양열 흡수식 냉각 시스템
- 제목 (타언어)
- Solar Absorption Cooling System applicable to Educational Facilities
- 저자
- 윤성민; 백인수; 한영태; 남효갑
- 발행일
- 2011-05
- 유형
- Y
- 저널명
- 교육시설
- 권
- 18
- 호
- 3
- 페이지
- 35 ~ 41