풍력발전단지 연계 전용선로 보호계전방식의 향상에 대한 연구
- 장성일;
- 김광호;
- 권혁완;
- 김대영;
- 권혁진
초록
- This paper describes the correction strategy of an overcurrent relay applied in the linked line for interconnecting wind farm with utility power networks in order to improve the capability of a fault detection. The fault current measured in a relaying point might vary according to the fault conditions. Generally, the current of the line to line fault or the line to ground fault in the linked line is much higher than the set value of protective relay due to the large fault level. However, when the high impedance fault occurs in the linked line, we can't detect it by conventional set value because its fault level may be lower than the generating capacity of wind farm. And, the protective relay with conventional set value may generate a trip signal for the insertion of wind turbine generators due to the large transient characteristics. In order to solve above problems and improve protective relaying algorithms applied in the linked line, we propose a new correction strategy of the protective relay in the linked line. The presented method can detect the high impedance fault which can't be detected by conventional relay set value and may prevent the mis-operation of protective relay caused by the insertion of wind farm.
키워드
- 제목
- 풍력발전단지 연계 전용선로 보호계전방식의 향상에 대한 연구
- 저자
- 장성일; 김광호; 권혁완; 김대영; 권혁진
- 발행일
- 2003-12
- 유형
- Y
- 저널명
- 전기학회논문지 A권
- 권
- 52
- 호
- 12
- 페이지
- 675 ~ 683