국내 수돗물의 부식성 특성 및 개선방안

Characteristics and Improvement of Tap Water Corrosivity in Korea
  • 김진근
  • 김영관

초록

To investigate corrosivity characteristics of tap water in Korea, Langelier index (LI) of 30 multi-regional water treatment plants (WTPs) were evaluated. Weekly LI values of 30 WTPs were all negative, which means tap water in Korea might be very corrosive. Maximum LI decrease through water treatment processes was 0.95 under no additional corrosion control process. Based on the correlation results between LI and tap water qualities, pH and calcium concentration were confirmed as major parameters for LI control. Addition of calcium hydroxide with CO_2 or calcium hydroxide or sodium hydroxide can be chosen based on water quality. Continuous monitoring of LI and related parameters is recommended in water distribution system.

키워드

Langelier indexinternal corrosioncorrosion controltap waterwater treatmentwater quality monitoring랑게리아 지수내부부식부식제어수돗물정수처리수질모니터링
제목
국내 수돗물의 부식성 특성 및 개선방안
제목 (타언어)
Characteristics and Improvement of Tap Water Corrosivity in Korea
저자
김진근김영관
발행일
2011-10
유형
Y
저널명
상하수도학회지
25
5
페이지
731 ~ 739