실내수영장 천장 내 결로 억제에 관한 실험적 연구

A study on Dew Condensation Control in the Ceiling of an Indoor Swimming Pool

초록

This paper measured the temperature and the humidity of the air in the ceiling depending on the operation and non-operation of an air-conditioner and a ventilation system for ceilings only. It was found that: in case of the only air-conditioner on and ventilation off appropriate thermal environment was maintained in the swimming pool and in the ceiling; and in case of the air-conditioner off and the ventilation on the relative humidity in the ceiling was maintained under 62%, so it was concluded that dew condensation gives a no influence on the safety of the inside of the ceiling. In case of the air-conditioner off and the ventilation off the relative humidity of the air in the ceiling was increased to about 78%. In this paper the quantity of energy consumption, was also measured depending on the operation of the air-conditioner and the ventilation system. It was found that the energy consumed for the operation of the air-conditioner per hour was about 625 times greater than that of the ventilation system.

키워드

Dew condensationIndoor swimming poolEnergy saving
제목
실내수영장 천장 내 결로 억제에 관한 실험적 연구
제목 (타언어)
A study on Dew Condensation Control in the Ceiling of an Indoor Swimming Pool
저자
이승철박영록박천수
발행일
2010-03
유형
Y
저널명
대한설비관리학회지
15
1
페이지
11 ~ 16