초록
The seismic evaluation of electric power facilities in the switchyard of nuclear power plants is currently insufficient. In order to evaluate the seismic performance of lightning arrester subjected to four types of earthquake (near- and far-fault earthquakes, NEHRP Site Class A&B and D earthquakes), seismic fragility analysis using maximum likelihood estimation is performed considering various damage states. The comparison of the seismic fragility curves for three main parts of lightning arrester that are the busing, anchor and steel frame, reveals that the failure of lightning arrester is governed by the bushing damage mode such as porcelain cracking.
키워드
Seismic fragility analysis; Electric power facilities; lightning arrester; Damage state
- 제목
- 다양한 손상상태를 반영한 피뢰기 설비의 지진취약도 해석
- 제목 (타언어)
- Seismic Fragility Analysis of Lightning Arrester Considering Various Damage States
- 저자
- 신유성; 송종걸
- 발행일
- 2014-01
- 유형
- Y
- 저널명
- 한국지진공학회논문집
- 권
- 18
- 호
- 1
- 페이지
- 19 ~ 28